Integrated LCD Meter for UPS Model 2034     TRMS

Model 2034-31

Model 2034-33

ADS 2034 is a Microcontroller based Universal Integrated Digital Meter to measure  AC Input Volt & Frequency, Output AC Volt, Current & Freq, DC Volt and Current of 3 Phase or 1 phase systems.

The Meter accepts normalised Inputs at 5V FSD. The general range available is 500V AC / DC, 100A AC/DC and Line frequency of 50 Hz. 

Model 2034-31 is suited for applications of 3 Phase Input and 1 phase Output.

 Model 2034-33 is suited for applications of 3 Phase Input and 3 phase Output.

      Features
  • Single meter measures 3Phase  Input AC Voltage & Frequency; Output AC Voltage, Current & Frequency, DC Voltage & Current
  • 4 Fault annunciation on Display
  • Micro controller based
  • Built-in selector switch
  • Back Lit Alphanumeric 16 X 2 LCD Display
  • 1% FSD Accuracy
  • Software calibration
  • Built-in digital noise filter to cater to harsh UPS field
  • Compact meter - 96mm X 96mm  - 20mm Depth
  • Optional RS 232 Output
Technical Specifications
Input Signal Input AC Volt 0-5V for 500V fsd 3 ch
Input frequenci from AC V channel
DC Volt 0-5V for 500V fsd
DC Amp   + & - 0-5V for 100A fsd
Model 2034-31 Output AC Volt 0-5V for 500V fsd 1 ch
Output AC Amp 0-5V for 100A fsd
Frequency from AC Volt
Model 2034-33 Output AC Volt 0-5V for 500V fsd 3 ch
AC Amp 0-5V for 100A fsd
Frequency from AC Volt
Accuracy better than 1% fsd
Display Alphanumeric LCD 16 X 2 back-lit
Auxillary Supply 9V to 12VDC
Package 96 X 96 mm facia ; 23mm depth
Termination Relimate connectors